ACS510 User's Manual
Fault
Code
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Fault Name In
Panel
Possible ground fault detected in the motor or motor cables. The drive
EARTH FAULT
monitors for ground faults while the drive is running and while the drive is
not running. Detection is more sensitive when the drive is not running and
can produce false positives.
Possible corrections:
• Check for/correct faults in the input wiring.
• Verify that motor cable does not exceed maximum specified length.
• A delta grounded input power supply and motor cables with high
capacitance may result in erroneous error reports during non-running
tests. To disable response to fault monitoring when the drive is not
running, use parameter 3023
ground fault monitoring, use parameter 3017
RESERVED
Internal fault. The thermistor measuring the internal temperature of the
THERM FAIL
drive is open or shorted. Contact your local ABB representative.
Internal fault. A communication-related problem has been detected on the
OPEX LINK
fiber optic link between the control and OINT boards. Contact your local
ABB sales representative.
Internal fault. Low voltage condition detected on OINT power supply.
OPEX PWR
Contact your local ABB representative.
Internal fault. Current measurement is out of range. Contact your local ABB
CURR MEAS
representative.
Ripple voltage in the DC link is too high. Check for and correct:
SUPPLY PHASE
• Missing mains phase.
• Blown fuse.
If this error code appears, refer to the appropriate accessory manual.
Not used.
RESERVED
Not used.
RESERVED
Internal fault. Configuration Block Drive ID is not valid. Contact your local
DRIVE ID
ABB sales representative.
Internal configuration file has an error. Contact your local ABB sales
CONFIG FILE
representative.
1
Fieldbus communication has timed out. Check for and correct:
SERIAL
ERR
• Fault setup (3018
• Communication settings (Group 51 or 53 as appropriate).
• Poor connections and/or noise on line.
Error in reading the configuration file for the embedded fieldbus.
EFB CON FILE
Fault trip forced by the fieldbus. See the fieldbus User's Manual.
FORCE TRIP
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
EFB
The meaning is protocol dependent.
2
EFB
3
EFB
Fault in the motor circuit. One of the motor phases is lost. Check for and
MOTOR PHASE
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
Description and Recommended Corrective Action
WIRING FAULT
COMM FAULT FUNC
. To disable response to all
.
EARTH FAULT
and 3019
).
COMM FAULT TIME
Diagnostics
199