4 SETUP AND PROCEDURES BEFORE STARTING THE OPERATION

4.3.2 Setting the mode (MODE)

MODE
4 - 5
Set the operation mode of the network module using the mode setting switch.
Set to Online (setting 0 or 4) after the standalone check (self-loopback test, internal
self-loopback test, and hardware test) of the network module is completed.
(a)
QJ71LP21, QJ71LP21G, QJ71LP21GE, QJ71BR11
Setting
0
1
2
3
4 to F
(b)
QJ71LP21-25, QJ71LP21S-25
Setting
0
1
2
3
4
5
6
7
8-F
Online (Mode selected with a network parameter becomes valid.)
Self-loopback test
Internal self-loopback test
Hardware test
Use prohibited
Online (Mode selected with a network parameter becomes valid.)
Self-loopback test
Internal self-loopback test
Hardware test
Online (Mode selected with a network parameter becomes valid.)
Self-loopback test
Internal self-loopback test
Hardware test
Use prohibited
MELSEC-Q
Description
Description
When
10Mbps
in use
When
25Mbps
in use
4 - 5