6 PROGRAMMING
No.
SB0002
System link startup
SB0003
System link stop
Cyclic transmission start
SB0050
acknowledgment status (system)
Cyclic transmission start completion
SB0051
status (system)
Cyclic transmission stop acknowledgment
SB0052
status (system)
Cyclic transmission stop completion
SB0053
status (system)
6 - 14
(Cyclic transmission restart)
8)
In the following link special register (SW), specify a station for restarting
cyclic transmission.
• Specification of target station
Link stop/startup direction content (SW0000)
• Specification of station No.
Link stop/startup direction content (SW0001 to SW0004)
9)
Turn System link startup (SB0002) ON.
10) When the network module accepts a request, Cyclic transmission start
acknowledgment status (system) (SB0050) is turned ON.
11) When the cyclic transmission restart is completed, Cyclic transmission
start completion status (system) (SB0051) is turned ON.
12) If the cyclic transmission restart is completed abnormally, an error code
will be stored in Data linking start status (entire system) (SW0051).
13) Turn System link startup (SB0002) OFF.
Description
No.
SW0000
Link stop/startup direction content
SW0001 to
SW0004
SW004A
Data linking stop request station
SW0051
Data linking start status (entire system)
SW0053
Data linking stop status (entire system)
MELSEC-Q
Description
6 - 14