Mitsubishi Electric Q Series Reference Manual page 260

Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

7 APPLICATION FUNCTIONS
Device
Item
(S1)+3
Target station CPU type
(S1)+4
Target station network No.
(S1)+5
Target station number
(S1)+6
(Use prohibited)
(S1)+7
Number of resends
(S1)+8
Arrival monitoring time
(S1)+9
Write data length
(S1)+10 (Use prohibited)
(S1)+11 Clock set flag
1: The setting side is as shown below.
User: It is data the user sets in the sequence program before execution of a link dedicated instruction.
System: The programmable controller CPU stores the execution result of the link dedicated instruction.
2: The CPU type can be specified when the host station is a network module of function version D or later.
(The specification is not available when they are other than the above. Access is made to the target station
CPU.)
3: If system switching occurs at the target system when the WRITE or SWRITE instruction is executed to the
redundant system with the control or standby system CPU designated, the instruction may not be normally
completed (error code: 4244
If the above-mentioned error occurs and the WRITE or SWRITE instruction is not normally completed, retry
to execute the instruction.
4: The CPU type can be specified when the QCPUs and network modules of the host station or target station
or the following versions.
(The specification is not available when they are other than the following. Access is made to the target
station CPU.)
Network module: First 5 digits of serial No. is "06092" or later
QCPU: First 5 digits of serial No. is "06092" or later
5: When a multiple CPU No. is specified for the target station CPU type ((S1)+3) and group designation (81
to A0
) or all stations (FF
H
for only the system where the CPU specified for the target station CPU type is the control CPU of the target
station.
Refer to Section 2.2.2 (5) for details.
7 - 58
Detailed description of the control data
Designate the CPU type of the target station.
Set value
Target station CPU/control CPU/host system CPU
0000
H
(The designation is the same as "03FF
03D0
2
Control system CPU
H
03D1
2
Standby system CPU
H
03D2
2
System A CPU
H
03D3
2
System B CPU
H
03E0
4
Multiple CPU No. 1 or target station CPU (in single CPU system)
H
03E1
4
Multiple CPU No. 2
H
03E2
4
Multiple CPU No. 3
H
03E3
4
Multiple CPU No. 4
H
03FF
2
Target station CPU/control CPU/host system CPU
H
Designates the network No. of the target station.
1 to 239 : Network No.
254
: Specify this when 254 has been set in Jn.
Designates the station number of the target station.
1 to 64
: The station with the corresponding station No.
81
to A0
: Group designation (Can be set when the execution type designated in (S1) is "0: No
H
H
arrival confirmation.")
5
FF
: All stations of the target network No. (Can be set when the execution type
H
designated in (S1) is "0: No arrival confirmation.") : excluding the host
When a group is designated, set the group No. of the target station with the network parameters from
GX Developer.
1) At instruction execution
Becomes valid when the execution type designated in (S1) is "1: With arrival confirmation." Set the
number of resends when the instruction fails to complete within the monitoring time designated by
(S1) + 8.
0 to 15 (times)
2) At instruction completion
Stores the number of resends executed (result).
0 to 15 (times)
Becomes valid when the execution type designated in (S1) is "1: With arrival confirmation." Set the
monitoring time until the instruction completion.
When the instruction fails to complete within the monitoring time, it is resent for the number of
resends designated in (S1) + 7.
0
: 10 s
1 to 32767
: 1 to 32767 s
Designates the number of write data in (S2) to (S2) + n. (Refer to Section 2.2.1)
1 to 960 (words)
Stores the valid/invalid status of the clock data in (S1) + 12 to (S1) + 17.
0: Invalid
1: Valid
, 4248
).
H
H
) is specified for the target station number ((S1)+5), the instruction is executed
H
Description
Description
.")
H
3
3
MELSEC-Q
Setting side
1
User
User
User
User
System
User
User
System
(Continued to the next page)
H
7 - 58