Mitsubishi Electric Q Series Reference Manual page 420

Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

APPENDIX
No.
Name
SW0044
Station setting
(68)
SW0046
Module type
(70)
SW0047
Baton pass status (host)
(71)
SW0048
Cause of baton pass
(72)
interruption
SW0049
Cause of data link stop
(73)
App - 19
Table 4 Link special register (SW) list (Continued)
Description
On inter-PLC network: Stores the condition setting switch status
of the host.
0: Off
1: On
b15b14
b13
b12
b11
b10
b9
b8
b7
b6
0 0
0
0
0
0
0
SW0044
Control station operation
(0: Switch to designated control station,
Operation mode
(0: Online mode, 1: Debug mode)
Host station network type
(0: MELSECNET/H mode, MELSECNET/10 mode,
1: MELSECNET/H Extended mode)
On remote I/O network: Stores the condition setting switch status
of the host.
0: Off
1: On
b15
to
b10
b9
b8 b7 b6
to
b2 b1 b0
SW0044
0
to
0
0
0
to
0
Return mode
(0: Master station returns as master operating station
(control station).
1: Master station returns as sub-master operating station
(standby station).)
Parameter status
(0: Without parameters for remote sub-master station
1: With parameters for master station and sub-master station)
Stores the network module type of the host.
b15 b14 b13
SW0046
0
01: Optical 10: Coaxial 11: Twisted
0: Duplex 1: Single
0: Loop 1: Bus
Stores the baton pass status of the host.
00
: Executing data linking
H
01
: Data linking stopped (instructed by other station)
H
02
: Data linking stopped (instructed by host)
H
03
: Executing baton pass (parameter received (no
H
transmission area in the host))
04
: Executing baton pass (parameter error)
H
05
: Executing baton pass (parameter not received)
H
06
: Being disconnected (no baton pass)
H
07
: Being disconnected (line error)
H
11
: Loop test
H
12
: Setup confirmation test
H
13
: Station order check test
H
14
: Communication test
H
1F
: Offline test
H
Stores the cause of baton pass interruption of the host.
0
: Normal communication
1
: Offline
2
: Offline test
3 or more
: Cause of interruption (see the error codes in
Section 8.3)
Stores the cause of data linking stop of the host.
0: Normal
1: Stop instructed
2: No common parameters
3: Common parameter error
4: Host CPU error
6: Communication aborted
to
b2
b1
b0
to
0
0
Network type
(0: PLC to PLC network)
Station type
(0: Normal station, 1: Control station)
1: Keep current control station)
1
Network type
(1: Remote I/O network)
Station type
(0: Multiplexed remote sub-master
station, remote I/O station
1: Multiplexed remote master station)
to
b2
b1 b0
to
0
MELSEC-Q
Use permitted/prohibited
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
Remote I/O
station
App - 19

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents