7 APPLICATION FUNCTIONS
7 - 51
Description of setting
Jn
Host's network No.
Start I/O number of the host's network module
Un
Designate the higher two digits of the 3-digit I/O number.
Control data storage head device
(S1)
Designate the head device of the host that stores the control
data.
Read data storage head device (target station)
(S2)
Designate the head device of the target station that stores the
data to be read.
Read data storage head device (host)
(D1)
Designate the head device of the host that stores the data to be
read.
Read completion device (host)
Designate the host's device to be turned on for one scan upon
(D2)
read completion.
(D2)
Off : Not completed
(D2)+1
Off : Normal
Read notification device (target station)
Designate the target station's device to be turned on for one
scan upon completion of the reading.
(D3)
(It can verify that the data in the target station has been read
from other station.)
(D3)
Off : Not completed
1: Bit device
2: Word device
3: Word device
4: Bit designation of word device : Word device. bit number
1 to 239
254: Network designated by valid module during
0 to FE
Word device
Word device
Word device
Bit device
Bit designation of word device
On : Complete
On : Error
Bit device
Bit designation of word device
On : Complete
: X, Y, M, L, F, V, and B
: T, C, D, W, ST, R, and ZR
(The Q00JCPU and QS001CPU cannot use
R and ZR.)
: T, C, D, W, ST, SD,SW, R, and ZR
(The Q00JCPU and QS001CPU cannot use
R and ZR.)
MELSEC-Q
Setting range
other station access
H
2
3
2
1
4
1
4
7 - 51