Hardware Test - Mitsubishi Electric Q Series Reference Manual

Hide thumbs Also See for Q Series:
Table of Contents

Advertisement

4 SETUP AND PROCEDURES BEFORE STARTING THE OPERATION

4.5.3 Hardware test

3
MODE
RUN
MNG
T.PASS
D.LINK
SD
RD
ERR.
L ERR.
4 - 13
This test checks the hardware inside the network module.
(1)
Connect the IN and OUT terminals of the QJ71LP21 network module (for the
optical loop system) with an optical fiber cable.
Do not connect cables or terminal resistors if the QJ71BR11 network module (for
the coaxial bus system) is used.
For QJ71LP21
(optical loop system)
IN
OUT
(2)
Set the model setting switch of the network module to "3". Set it to "7" when
using the QJ71LP21-25 at 25Mbps.
The hardware test is selected.
(3)
Switch power on.
The hardware test is executed; check the execution status on the network
module display.
The T. PASS LED flashes during the test.
When the T. PASS LED flashes 20 times or more and if the ERR.LED does not
flash, this condition indicates normal completion.
If the test is abnormally completed, the ERR. LED flashes.
Upon detection of an error, the test will be terminated (abnormal termination).
Before test
T.PASS : Off
When an error occurs, the contents of the error should be checked with GX
Developer. The faulty area can be examined by replacing the cable or module.
REMARKS
In the MELSECNET/H, a link refresh is executed even when the module is offline.
Thus, the user can check the testing status and the result with GX Developer or a
sequence program using the link special registers.
Baton pass status (host)
Cause of baton pass interruption
Offline test execution item/faulty
station (requesting side)
Offline test result (requesting side)
For details on how to check the error contents, see Chapter 8.
If two or more modules are installed, the testing status and the result of each module
can be checked by adding 200
For QJ71BR11
(coaxial bus system)
Connect IN
and OUT
During test
Normal completion of test
: Flashing
: Flashing 20 times (approx. 10 seconds) or
more
Abnormal completion of test
ERR.
: Flashing
SW0047
SW0048
SW00AC
SW00AD
to the corresponding device number.
H
MELSEC-Q
Do not connect
anything
1F
: Offline test
H
2
: Offline test
H
9
: Hardware test
H
0
: Normal
1 or larger : Error code
4 - 13

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents