8 TROUBLESHOOTING

8.1.2 Other station information

1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
8 - 7
On the other station information screen, information such as the communication, data
link, parameter, CPU, loop and reserved station statuses of each station can be
checked.
[Network info.]
This area displays the same information as the host information in Section 8.1.1.
[Other station info.]
When any STOP-status station, reserved station and/or externally-powered
station is detected for 1) to 8) and 12), the following mark(s) is displayed in the
error information area. (For 9) to 11), "ERR" is not displayed.)
When a faulty or STOP-status station is detected
When a reserved station exists
When power is supplied to a module with external power supply
By clicking each item button, the corresponding status of each station is
displayed.
This information is displayed for the number of stations that equals to the "total
number of link stations" set with the network parameters.
1)
Communication status of each station (SW0070 to 73)
Displays the status of the baton pass (whether or not the transient
transmission is possible).
• Normal display
• Highlighted display
Status
: Communication normal station or reserved station
: Communication error station (disconnected status)
MELSEC-Q
Display
ERR
RSV
PWR