Legend To The Sequence Diagrams - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Legend to the
sequence diagrams
Depending on the parameter, VP takes place:
between Ph 62 and 70 and / or
between Ph 30 and 32
Signal
Signal
ON
0 - 3 s
1)
Parameter:
2)
Parameter:
3)
Delayed shutdown within ts
4)
Parameter:
5)
Parameter:
Normal startup
Direct startup
6)
Sequential phase = 24
7)
Only with valve proving during startup
8)
Parameter:
9)
Parameter:
10)
Fan controlled as before
Running time when locked out = T_FanLockout
11)
Parameter:
12)
With valve proving in startup phase 10
13)
Parameter:
Normal purging:
Continuous purging: Checking for on in 10 and 12,
46/157
Siemens Building Technologies
HVAC Products
Next
OFF
phase
00, Rep = 0
01
12, Rep > 0
Parameter direct start
Checking with controller on
Devation --> 10
No Rep decrement
10
70
Without VP 70
With VP 80
62
Stop, up to Ph -
Max. time
01
Stop, up to Ph -
Max. time
10
00, Rep = 0
01
12, Rep > 0
0 - 3 s
00, Rep = 0
01
12, Rep > 0
0 - 30 s
00, Rep = 0
01
12, Rep > 0
79
Param.
10
Input : Don't care
Output : OFF
Output : ON
7550f20E/0601
With / without PM
Short / long preignition time
for oil only
short / long oil pump
ON time
Output as startup signal /
PM relief valve
Normal / direct startup
sequential phase = 10
sequential phase = 79
(when R = ON)
With / without alarm
on prevention of startup
With continuous purging
With / without extraneous light
test in standby
Normal / continuous purging
Checking for off in 10,
Stop to Ph-max time -> 01
Stop to Ph-max time -> 01
Basic Documentation LMV51...
3 Burner control
Assignment of times :
t0
Postpurge lockout position
t01
MaxT_SafetyPhase
t10
MinTimeHomeRun
t21
MinT_StartupRel
t22
FanRunupTime
tv
PrepurgeTime_Gas / Oil
t30
PrepurgePt1
PrepurgePt3
t34
t36
MinOnT_OilPump
t38
PreignitionT_Gas / Oil
PreignitionT_Off
t42
ts1
SafetyTime1 Gas / Oil
t44
Interval1 Gas / Oil
t50
SafetyTime2 Gas / Oil
t52
Interval2 Gas / Oil
t62
MaxTimeLowFire
t70
AfterburnTime
t74
PostpurgeT1 Gas / Oil
t78
PostpurgeT3 Gas / Oil
t80
VP_EvacTime
t81
VP_TimeAtmPress
t82
VP_FillTime
t83
VP_TimeGasPress
tmx1
MaxDampRunTime
tmx2
MaxT_ StartupRel
tmx3
MaxT_CircHOil
Permissible positioning range
In standby : actuator can travel within
the permissible positioning range, but
is always driven to the home position.
Must be in the home position before
changing the phase
90° :
Actuator fully open (90°)
HF :
Pre-Purge position
PoP :
Post-Purge position
IGN :
Ignition position
LF :
Low-Fire position
HP :
Home position
0° :
Position as supplied
AD
Air Damper
CPI
Closed Position Indicator
APS
Air Pressure Switch
FCC
Fan Contactor Contact
FGR
Flue Gas Recirculation
PS
Pressure Switch
PoP
Post-Purge
PrP
Pre-Purge
PS-VP Pressure Switch-Valve Proving
SLT
Safety Limit Thermostat
SR
Safety Relay
TL
Temperature Limiter
CC1P7550en