"ER"
Block (hex)
LED
4x
0xE4FE8C00
--
0xE4FE8D00
--
0xE4FE8E00
--
0xE5FE0100
--
0xE5FE0200
--
0xE5FE0400
--
0xE5FE0500
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
Operating Instructions, 04/2020, C79000-G8976-C512-03
Error description
Communication error between Ident profile and communication module. Handshake error.
Possible causes / action to be taken:
The UDT of this communication module has been overwritten by other program sections.
Check the parameter settings of the communication module in the UDT.
Check the Ident profile command that causes this error.
After eliminating the error, execute the "INIT" command.
Backplane bus / PROFIBUS DP error occurred.
This error is only indicated when access monitoring has been enabled in the PROFIBUS con-
figuration.
Possible causes / action to be taken:
Backplane bus / PROFIBUS DP bus connection was interrupted (wire break on the bus;
bus connector on the communication module was briefly unplugged)
The backplane bus / PROFIBUS DP master no longer addresses the communication
module
Execute the "INIT" command.
The communication module has detected a frame interruption on the bus. The backplane
bus, PROFIBUS may have been re-configured (e.g. with HW Config or TIA Portal)
Firmware error
Possible causes:
The firmware update was not run completely.
Internal communication error of the communication module/reader
Possible causes / action to be taken:
Connector contact problem on the communication module / reader
Hardware of the communication module/reader has a defect; → Send in communication
module/reader for repair.
After eliminating the error, execute the "INIT" command.
Internal monitoring error of the communication module/reader
Possible causes / action to be taken:
Program execution error on the communication module / reader
Switch supply voltage to communication module/reader off and on again.
After eliminating the error, execute the "INIT" command.
The current command was aborted by the "WRITE-CONFIG" ("INIT" or "SRESET") command for
the bus connector was pulled.
Possible causes:
Communication with the transponder was aborted by "INIT".
This error can only be reported if there is an "INIT" or "SRESET".
Incorrect sequence number order (SN) on the reader/communication module
Incorrect sequence number order (SN) in the Ident profile
Invalid data block number (DBN) on the reader/communication module
Invalid data block number (DBN) in the Ident profile
Service and maintenance
12.2 Error messages