"ER"
Block (hex)
LED
4x
0xE4FE8C00
--
0xE4FE8D00
--
0xE4FE8E00
--
0xE5FE0100
--
0xE5FE0200
--
0xE5FE0400
--
0xE5FE0500
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
Operating Instructions, 04/2020, C79000-G8976-C512-03
Error description
Communication error between Ident profile and communication module. Handshake error.
•
Possible causes / action to be taken:
–
The UDT of this communication module has been overwritten by other program sections.
–
Check the parameter settings of the communication module in the UDT.
–
Check the Ident profile command that causes this error.
–
After eliminating the error, execute the "INIT" command.
Backplane bus / PROFIBUS DP error occurred.
•
This error is only indicated when access monitoring has been enabled in the PROFIBUS con-
figuration.
Possible causes / action to be taken:
–
Backplane bus / PROFIBUS DP bus connection was interrupted (wire break on the bus;
bus connector on the communication module was briefly unplugged)
–
The backplane bus / PROFIBUS DP master no longer addresses the communication
module
–
Execute the "INIT" command.
–
The communication module has detected a frame interruption on the bus. The backplane
bus, PROFIBUS may have been re-configured (e.g. with HW Config or TIA Portal)
Firmware error
•
Possible causes:
The firmware update was not run completely.
Internal communication error of the communication module/reader
•
Possible causes / action to be taken:
–
Connector contact problem on the communication module / reader
–
Hardware of the communication module/reader has a defect; → Send in communication
module/reader for repair.
–
After eliminating the error, execute the "INIT" command.
Internal monitoring error of the communication module/reader
•
Possible causes / action to be taken:
–
Program execution error on the communication module / reader
–
Switch supply voltage to communication module/reader off and on again.
–
After eliminating the error, execute the "INIT" command.
The current command was aborted by the "WRITE-CONFIG" ("INIT" or "SRESET") command for
the bus connector was pulled.
Possible causes:
Communication with the transponder was aborted by "INIT".
•
This error can only be reported if there is an "INIT" or "SRESET".
•
Incorrect sequence number order (SN) on the reader/communication module
Incorrect sequence number order (SN) in the Ident profile
Invalid data block number (DBN) on the reader/communication module
Invalid data block number (DBN) in the Ident profile
Service and maintenance
12.2 Error messages
159