Service and maintenance
12.3 Firmware update
12.3.2

Update firmware via TIA Portal (STEP 7 Basic / Professional)

This section is intended only for S7 users.
Requirements
● The communication module is connected to the controller or PC via Industrial Ethernet.
● The IP address of the communication module is stored in the module parameters.
● The communication module has been separated from running operation.
Note that performing the update while the application is running can slow down both the
update and command processing.
● The required update files were stored locally.
Procedure
Proceed as follows to perform a firmware update of the communication module via STEP 7
Basic / Professional (TIA Portal):
1. Start the TIA Portal.
2. Open your existing project and change to the project view.
3. Change to the network view.
4. Right-click on the desired communication module and click on "Online & Diagnostics" in
the shortcut menu.
5. Select the entry "Functions > Firmware Update via Web Interface".
6. Click on the "Web Diagnostics" button.
Reaction: The WBM of the communication module opens in your Web browser.
Figure 12-3
Firmware update of the communication module
7. Continue the firmware update as described in the section "Updating the firmware via
WBM (Page 167)".
168
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
Operating Instructions, 04/2020, C79000-G8976-C512-03