17  Technical Data

17 Technical Data

17.1 Sunny Central 500CP XT

Input Data
MPP voltage range
Maximum DC voltage
Maximum DC current
Maximum short-circuit current
Overvoltage category - DC inputs
Overvoltage category - AC inputs
Overvoltage category - communication
Number of DC Inputs
Maximum number with DC fuse
Maximum number with DC fuse with SMB Connection Kit
Maximum number with DC busbar
Fusing
Fuse sizes with DC fuse*
Fusing with DC busbar
* Screening factor: 0.7
Output Data
Nominal AC power at +50°C
Continuous AC power at +25 °
Maximum AC current
Nominal AC current
Nominal AC voltage − 10% / +15%
Power frequency
Displacement power factor cos φ
Maximum total harmonic distortion
Overvoltage category - AC output
Overvoltage category - communication
Power Consumption
Self-consumption in operation
Standby consumption
External supply voltage
76
SCCPXT-IA-D7-en-42
430 V
DC
1,000 V
1,250 A
1,680 A
9 per potential
24 per potential
2 per potential
125 A / 160 A / 200 A / 250 A / 315 A / 400 A
in DC main distribution
500 kVA
550 kVA
1,176 A
1,069 A
270 V
50 Hz / 60 Hz
0.9
lagging
< 3%
< 1,900 W
< 100 W
230 V / 400 V (3/N/PE), 50 Hz / 60 Hz
SMA Solar Technology AG
to 850 V
DC
DC
DC
DC
II
III
II
AC
AC
AC
to 0.9
leading
III
II
Installation Manual