Technical Data; General Data; Dc Input - SMA SUNNY TRIPOWER CORE2 Operating Manual

Hide thumbs Also See for SUNNY TRIPOWER CORE2:
Table of Contents

Advertisement

SMA Solar Technology AG

16 Technical Data

16.1 General Data

Width x height x depth
Weight with enclosure lid and connecting plate
Length x width x height of the packaging
Transport weight
Climatic category in accordance with IEC
60721‑3‑4
Environmental category
Pollution degree of all enclosure parts
Operating temperature range
Maximum permissible value for relative humid-
ity, condensing
Maximum operating altitude above mean sea
level (MSL)
Typical noise emission
Power loss in night mode
Power control / Demand response (DRED)
Export limiting in accordance with AS/
NZS 4777.2
Demand response mode in accordance with
AS/NZS 4777.2
Topology
Cooling method
Number of fans
Degree of protection for electronics in accor-
dance with IEC 60529
Protection class in accordance with
IEC 62109-1

16.2 DC Input

Maximum PV array power
Maximum input voltage
MPP voltage range
Operating manual
1117 mm x 682 mm x 363 mm
93.5 kg
1220 mm x 840 mm x 618 mm
125 kg
4K4H
Outdoors
2
-30°C to +60°C
100 %
3000 m
78 dB(A)
< 5 W
Communication via Modbus interface
EDMM-10, EMETER-20
DRM0
Transformerless (Non-isolated)
Active cooling
5
IP66
I
165000 Wp STC
1100 V
200 V to 1000 V
STP110-60-BE-en-16