Expanded Function Mode Of C Group; Input Terminal Function - Hyundai hirun N100 plus Instruction Manual

Vector inverter
Hide thumbs Also See for hirun N100 plus:
Table of Contents

Advertisement

plus
N100 INSTRUCTION MANUAL

Expanded Function Mode of C Group

Func-
Func-
Name
Name
code
code
Input TerminalFunction
Intellingent Input
C01
terminal 1 setting
Intellingent Input
C02
terminal 2 setting
Intellingent Input
C03
terminal 3 setting
Intellingent Input
C04
terminal 4 setting
Intellingent Input
C05
terminal 5 setting
Intellingent Input
C06
terminal 6 setting
Input Terminal 1
a/b contact setting
C07
(NO/NC)
Input Terminal 2
a/b contact setting
C08
(NO/NC)
Input Terminal 3
a/b contact setting
C09
(NO/NC)
Description
Description
Select function for terminal 1
<code> 0: Forward run command(FW)
1: Reverse run command(RV)
2: 1 multi-speed command(CF1)
st
3
: 2 multi-speed command(CF2)
nd
4: 3 multi-speed command(CF3)
rd
5: 4 multi-speed command(CF4)
th
6: Jogging operation command(JG)
7: 2nd function setting command(SET)
8: 2-stage acceleration/deceleration command(2CH)
9: free-run stop command(FRS)
10:external trip(EXT)
11:unattended start protection(USP)
12:software lock function(SFT)
13.analog input current/voltage selection signal(AT)
14:reset(RS)
Select function for terminal 2
<code>-see C01 parameter
Select function for terminal 3
<code>-see C01 parameter
Select function for terminal 4
<code>-see C01 parameter
Select function for terminal 5
<code>-see C01 parameter
Select function for terminal 6
<code>-see C01 parameter
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC]
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC]
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC]
Run-
Defaults
Defaults
time
Edit
0
1
2
3
8
14
0
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents