Multi-Speed Frequncy Setting - Hyundai hirun N100 plus Instruction Manual

Vector inverter
Hide thumbs Also See for hirun N100 plus:
Table of Contents

Advertisement

plus
N100 INSTRUCTION MANUAL
Func-
Name
code
External
frequency
A07
start rate setting
External
frequency
A08
end rate setting
External
frequency start
A09
pattern setting
External
frequency
A10
sampling setting

Multi-speed Frequncy Setting

Multi-speed
A11
frequency
setting
A25
Jogging
frequency
A26
setting
Jogging stop
operation
A27
selection
Description
The starting point(offset) for the active
analog input range(0 10V, 4mA 20mA)
setting range is 0 to 100% in units of 0.1%
The ending point(offset) for the active
analog input range(0 10V, 4mA 20mA)
setting range is 0 to 100% in units of 0.1%
Two options: select codes:
Frequency
A06
A09=0
A05
A09=1
4V
A07
4mA
0.... start at start frequency
1.... start at 0Hz
Range n = 1 to 8, where n = number of
samples for average
Defines the first speed of a multi-
speed profile, range is 0 to 400Hz in
units of 0.01Hz.
Setting range is 1-speed(A11) to
15-speed(A25).
Speed0:volume setting value
Defines limited speed for jog,
range is 0.5 to 10.00Hz in units of 0.01Hz.
The jogging frequency is provided safety
during manual operation.
Define how end of jog stops the motor:
three options:
0.... Free-run stop
1.... Deceleration stop(depending on
deceleration time)
2.... DC braking stop(necessarg to set
DC braking)
Analog input
10V
20mA
A08
Run-
Defaults
time
Edit
0.0%
100.0%
0
4
Samples
speed1:5Hz
speed2:10Hz
speed3:15Hz
speed4:20Hz
speed5:30Hz
speed6:40Hz
speed7:50Hz
speed8:60Hz
etc. 0Hz
0.50Hz
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents