Run Signal [RUN]
When the [RUN] signal is selected as an intelligent output terminal, the inverter
outputs a signal on that terminal when it is in the Run Mode. The output logic
is active low, and is the open collector type (switch to ground)
Run
command
FW[RV]
Motor
speed
Run
signal
Terminal
Option
Symbol
Code
0
RUN
Valid for inputs:
Required setting
Notes:
The inverter outputs the [RUN] signal
whenever the inverter output exceeds the
start frequency . The start frequency is the
initial inverter output frequency when it
turns on.
NOTE : The example circuit in the table above drives a relay coil. Note the use
of a diode to prevent the negative-going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name

Run signal

C13, C14
(none)
ON
Input
Description
State
ON
when inverter is in Run Mode
when inverter Stop Mode
OFF
Example:
CM2
50 max
DC 27Vmax
DC braking
ON
Open collector output
RUN
12
11
RY