4.2.4

Expanded Function Mode of A Group

Func-
code
Basic parameter settings
Frequency command
A01
(Multi-speedcommand
method)
A02 Run command
A03 Base frequency setting
Maximum frequency
A04
setting
Analog Input Settings
External frequencysetting
A05
start (O, OI)
External frequencysetting
A06
end (O, OI)
External frequencystart rate
A07
setting (O, OI)
External frequencyend rate
A08
setting (O, OI)
Run-
Name
time
Edit
X
X
X
X
X
X
X
X
Description
Four options: select codes:
0.... Keypad potentiometer
1.... Control terminal input
2.... Standard operator
3.... Remote operator(1
4.... Remote operator(2
Set the method of run commanding:
0.... Standard operator
1.... Control terminal input
2.... Remote operator(1
3.... Remote operator(2
Settable from 0 to maximum frequencyin units of
0.01Hz
Settable from the base frequency [A03]
up to 400Hz in units of 0.01 Hz.
In the case of sensorless vector control,
possible for driving to 300Hz
Start frequency provided when analog
input is 0V (4mA) can be set in
units of 0.01Hz setting range is 0 to maximum
frequency(A04)
End frequency provided when analog
input is 10V(20mA) can be set in units
of 0.01Hz. setting range is 0 to maximum
frequency(A04)
The starting point(offset) for the active
analog input range(0∼10V, 4mA∼20mA)
setting range is 0 to 100% in units of 0.1%
The ending point(offset) for the active
analog input range(0∼10V, 4mA∼20mA)
setting range is 0 to 100% in units of 0.1%
4-8
ST
communication-RJ45)
ND
communication-terminal)
ST
communication-RJ45)
ND
communication-terminal )
Defaults
1
1
60.00Hz
60.00Hz
0.00Hz
0.00Hz
0.0%
100.0%