Dc Braking Settings; Frequency-Related Functions - Hyundai hirun N100 plus Instruction Manual

Vector inverter
Hide thumbs Also See for hirun N100 plus:
Table of Contents

Advertisement

plus
N100 INSTRUCTION MANUAL
Func-
Name
code

DC Braking Settings

DC braking
A33
function selection
DC braking
frequency
A34
setting
DC braking
output delay
A35
time setting
DC braking
A36
force setting
DC braking
A37
time setting

Frequency-related Functions

Frequency
upper
A38
limit setting
Frequency
lower limit
A39
setting
A40
Jump(center)
frequency
A42
setting
A44
Description
Sets two options for DC braking
0.... Disable
1.... Enable
The frequency at which DC braking
occurs, range is 0.0 to 10.0 Hz in units
of 0.01Hz
The delay from the end of Run command
to start of DC braking (motor free runs
until DC braking begins).
Setting range is 0.0 to 5.0sec in units of
0.1set.
Running
+
0
-
Applied level of DC braking force,
settable from 0 to 50% in units of 0.1%
Sets the duration for DC braking, range
is 0.0 to 10.0 seconds in units of 0.1sec.
Sets a limit on output frequency less than
the maximum frequency(A04). Range is
0.00 to 400.0Hz in units of 0.01Hz.
Output frequency
Upper
A38
limit
Lower
A39
limit
Sets a limit on output frequency greater
than zero. Range is 0.00 to 400.0Hz in
units of 0.01Hz
Up to 3 output frequencies can be defined
for the output to jump past to avoid motor
resonances(center frequency) range is
0.00 to 400.0Hz in units of 0.01Hz.
Free run DC braking
time
A 35
A 37
Settable range
Frequency command
Run-
time
Defaults
Edit
0
0.50Hz
0.0sec
10.0%
0.0sec
0.00Hz
0.00Hz
0.00Hz