Intelligent Input Terminal Function - Hyundai hirun N100 plus Instruction Manual

Vector inverter
Hide thumbs Also See for hirun N100 plus:
Table of Contents

Advertisement

plus
N100 INSTRUCTION MANUAL

8.3 Intelligent Input Terminal Function

Forward Run/Stop[FW] and Reverse Run/Stop Command[RV]
When you input the Run command via the terminal [FW], the inverter executes
the Forward Run command (high) or Stop command(low).
When you input the Run command via the terminal [RV], the inverter executes
the Reverse Run command(high) or Stop command(low).
Terminal
Option
Symbol Function Name State
Code
0
FW
1
RV
Valid for inputs:
Required setting
Notes:
When the Forward Run and Reverse
Run commands are active at the same
time, the inverter enters the Stop Mode.
When a terminal associated with either
[FW] or [RV] function is configured for
normally closed, the motor starts rot-
ation when that terminal is discon-
nected or otherwise has no input
voltage. Set the parameter
1
DANGER : If the power is turned on and the Run command is already
active, the motor starts rotation and is dangerous! Before turning power on,
confirm that Run command is not active.
Forward Run/
Stop
Reverse Run/
Stop
C01,C02,C03,C04,
C05,C06
A02=01
to
A 02
Inverter is in Run Mode, motor
ON
runs forward
Inverter is in Run Mode, motor stop
OFF
Inverter is in Run Mode, motor
ON
runs reverse
Inverter is in Run Mode, motor
OFF
runs stop
Example:
CM1 6
Description
RV FW
5
4
3
2
SWR SWF
1 P24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents