plus
N100 INSTRUCTION MANUAL
Func-
Func-
Name
Name
code
code
Electronic Thermal Overload Alarm Setting
Electronic
b04
thermal
level setting
Electronic
b05
thermal
characteristic,
selection
Overload Restriction
Overload
overvoltage
b06
restriction
mode selection
Overload
restriction
b07
level setting
Overload
restriction
b08
constant setting
Description
Description
Set a level between 20% and 120% for
the rated inverter current.
setting range- 0.2
current) 1.2
Select from two curves, option codes:
0....(SUB) reduced torque characteristic
1....(CRT) constant torque characteristic
Constanttorque(CRT)
100
80
output
60
current
Reducedtorque(SUB)
0
5
Select overload or overvoltage restriction
mode;
0.... O
verload,overvoltage restriction
mode OFF
1....
Overload restriction mode ON
2....
Overvoltage restriction mode ON
3....Overload,overvoltage restriction
mode OFF
Sets the level for overload restriction,
between 20% and 200% of the rated
current of the inverter, setting range- 0.2
( inverter rated current) 2.0 ( inverter
rated current).
Set the deceleration rate when inverter
detects overload,
range is 0.1 to 10.0 and
resolution is 0.1
Motor
Current
Output
frequency
(inverter rated
(inverter rated current).
20
60
120
Outputfrequency(Hz)
b08
Run-
Defaults
Defaults
time
Edit
100.0%
125.0%
b07
1.0sec
1
1