Expanded Function Mode Of A Group - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
`
4.2.4

Expanded Function Mode of A Group

Func-
Name
code
Basic parameter settings
Frequency command
A01
(Multi-speed command
method)
A02
Run command
A03
Base frequency setting
Maximum frequency
A04
setting
Analog Input Settings
External frequency setting
A05
start (O, OI)
External frequency setting
A06
end (O, OI)
External frequency start
A07
rate setting (O, OI)
External frequency end
A08
rate setting (O, OI)
Run-
time
Edit
Four options: select codes:
0.... Keypad potentiometer
1.... Control terminal input
X
2.... Standard operator
3.... Remote operator(communication)
4.... Remote operator2(IO Board) - Option
Set the method of run commanding:
0.... Standard operator
X
1.... Control terminal input
2.... Remote operator(communication)
3.... Remote operator2(IO Board) - Option
Settable from 0 to maximum frequency in units of
0.01Hz
V
100%
X
Settable from the base frequency [A03]
up to 400Hz in units of 0.01 Hz.
X
In the case of sensorless vector control, (A31=2)
possible for driving to 300Hz
Start frequency provided when analog input is
0V (4mA) can be set in units of 0.01Hz setting
range is 0 to 400 Hz
X
End frequency provided when analog input is 10V
X
(20mA) can be set in units of 0.01Hz. Setting range is
0 to 400Hz
The starting point(offset) for the active
X
analog input range(0∼10V, 4mA∼20mA)
setting range is 0 to 100% in units of 0.1%
The ending point(offset) for the active
X
analog input range(0∼10V, 4mA∼20mA)
setting range is 0 to 100% in units of 0.1%
4-8
Description
(A04)
Base
Maximum
frequency
frequency
(A03)
Frquency
(A06)
(A05)
(A08)
(A07)
0V
10V
Analog input
4mA
20mA
Defaults
1
1
60.00Hz
60.00Hz
0.00Hz
0.00Hz
0.0%
100.0%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents