Technical Support Document for Inverter Doc. No. TSD-N100-COM-001E(00) Model All N100 model Rev. Date August, 2008 plus N100 Inverter RS485 Interface Instruction Manual...
Inverter RS485 Interface Instruction Manual RS485 Communication function Communication function Communication circuit for RS485 is built in N100 Inverter. It is possible to control 1~32 Inverters (Slave) from a main control device (Master) by using RS485 serial communication is supported.
N100 Inverter RS485 Interface Instruction Manual 1.1.2 Interface Cable Pin Arrangement PC(or PLC) ~ Inverter Wiring Diagram RS232 To RS485 Converter RS232 RS485 Note If the PLCs have a RS485 communication port, don’t use the converter (RS232 to RS485 converter) between the PLCs and inverter.
N100 Inverter RS485 Interface Instruction Manual 1.1.3 RS485 Communication specification Item Specification Notes Communication RS485 interface Communication methods Half duplex communication methods Transmission speed 9600[BPS] (Baud Rate) Response for the external read, write The inverter operates only as Start methods command slave.
N100 Inverter RS485 Interface Instruction Manual 1.1.5 Communication order The flow of the communication protocol between an external control device and an inverter is shown below in the time diagram. External control Frame 1 Devices Frame 2 Inverter Waiting time (setting with operator) Fig.
N100 Inverter RS485 Interface Instruction Manual 1.2.1 Inverter read frame It requires 1~8 parameters of Inverter. (1) External controller transmit frame Communication Parameter Command parameter CRC Hi CRC Lo number count Clause Description Data size Specifications Communication Inverter communication...
N100 Inverter RS485 Interface Instruction Manual 1.2.2 Request frame for setting parameter Setting 1 parameter and command (note3) of Inverter (1) External transmit frame Communication Order Parameter Data CRC Hi CRC Lo number Clause Description Data size Specifications Communication...
Page 9
N100 Inverter RS485 Interface Instruction Manual (3) Parameter setting [Note 1] ① Basic parameter 1st byte : Each group is setting. Group byte Group byte 0x01 0x05 0x02 0x06 0x03 0x07 0x04 Table 7 Basic parameters (1 byte) byte : Parameter number setting...
Page 10
N100 Inverter RS485 Interface Instruction Manual (4) Data value setting [Note 2] Data value is transmitted except decimal point. Ex1) Output frequency Parameter value Communication data Converted hexadecimal value 1st byte : 0x17 60.00Hz 6000 2nd byte : 0x70...
Page 11
N100 Inverter RS485 Interface Instruction Manual ② Frequency command Parameter 1st byte : 0x00 2nd byte : 0x04 Setting data Output frequencyⅹ100 Ex) The case of output frequency command is 60 Hz Data 6000 transmit 1st byte : 0x17...
Page 12
N100 Inverter RS485 Interface Instruction Manual Ex) The case of d001 output frequency reading. Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Communication Command Parameter Parameter number number 0x01 0x03 0x01 0x01 0x00 0x01 The sequence of addition Byte(0x01) 16Bit Register...
N100 Inverter RS485 Interface Instruction Manual Frequency Command 2.3.1 A prior condition (1) Communication number : (Inverter address 1) (2) Command (Setting request) (3) Parameter 0004 2.3.2 Example 6 – Frequency Command (In case of 60Hz) (1) Transmit Data (In case of 60.00Hz) Com.