3.1.11
Low Pressure Protection Control
The following control is provided to protect the compressors from abnormal decrease of low pressure (LP).
[Cooling mode]
LP<0.15MPa
Normal operation
·LP>0.20MPa
·&
·30 sec elapse
OR
·Ta<Tes+5
[Heating mode]
LP<0.08MPa
Normal operation
LP > 0.13 MPa
Upper limit frequency =
Maximum frequency
[Oil return mode (common for cooling / heating)]
Function UM Combination "MA1R Series" Using R-407C
·LP<0.08MPa
·&
·Ta>5˚C
OR
·LP<0.049MPa
·&
·Ta≤5˚C
Compressor
SVP (for hot gas
operation
bypass) : ON
frequency
31Hz+OFF+OFF
·LP>0.13MPa
·&
·Ta>5˚C
OR
·LP<0.098MPa
·&
·Ta≤5˚C
LP<0.05MPa
Restriction for upper
SVP (for hot
limit compressor
gas bypass) : ON
operation frequency ∗1
1-step increase for
compressor
operation frequency
LP<0.05MPa
SVP (for hot gas
SVP (for hot gas
bypass) : OFF
bypass) : ON
LP>0.10MPa
Ta : Outdoor air temp. (˚C)
Tes : Low pressure equivalent
saturation temp. (˚C)
LP<0.03MPa
Forced thermostat
OFF
LP>0.10MPa
(Monitoring LP every 30 sec.)
LP>0.07MPa
(Monitoring LP every 1 min)
Outline of Control
LP<0.0MPa
E4 malfunction
stop
∗ Malfunction reset
LP>0.09MPa
(V0822)
437