Panasonic Urban Multi MX1R Series Service Manual page 620

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
6.1.2
Wiring
„ Combined use of constant contact (a) and instantaneous contact (a)
Operation Signal
„ Combined use of voltage 12~24 VDC, no voltage
„ Remote control mode selector switch (Control contents differ according to input mode. See the following
Control Mode
„ Display of malfunction signal (no voltage contact [a])
Display Signal
„ Display of operation (no voltage contact [a])
Fetch
‹ For voltage input, approximately 10 mA of input current per contact is required.
Note:
‹ In the case of input, use a micro-current contact as the input contact.
‹ There is no polarity for voltage input.
‹ Temperature input is resistance value input of 0~135
Appendix
page for details.)
Remote temperature setting (Can be set from 16~32°C.)
Either plus common or minus common can be used for terminal BC.
.
Interface Adaptor
599