Panasonic Urban Multi MX1R Series Service Manual page 625

Using r-407c / r-22
Table of Contents

Advertisement

Interface Adaptor
„ Remote control mode selector switch (RS1) setting
Position
Note:
Forced off (disregard input A) is effected when using input B constant input at positions 7~A. Input B
constant input cannot be used by B.
‹ Example of when the remote control selector switch (RS1) is set to No. 6
604
Function
0
Disregard input
1
Remote controller
inhibited
2
Central priority
3
Remote controller
permitted / inhibited
4
Remote controller
permitted / inhibited /
OFF
5
Remote controller
inhibited
6
Individual
7
Remote controller
inhibited
8
Central priority
9
OFF by remote controller
permitted
A
Remote controller
permitted / inhibited /
OFF
B
Individual
C
Mode 5 + energy
efficiency control
D
Mode 5 + room
temperature setting shift
E
Mode 6 + energy
efficiency control
F
Mode 6 + room
temperature setting shift
Below are remote control commands relative to input signal and indoor unit time chart
Operation by input mode A and B
Input A (between B1~Bc)
Operates by ON and stops by OFF
Operates by ON (remote controller
permitted) and stops by OFF (remote
controller inhibited)
Same as mode 1 (OFF by remote
controller always permitted)
ON by remote controller permitted, stops
by OFF (remote controller inhibited)
ON / OFF (cyclic)
Same as mode 5 (only OFF by remote
controller always permitted)
Operates by ON
Operates by ON (remote controller
permitted)
Same as mode 7 (OFF by remote
controller always permitted)
ON by remote controller permitted
Same as mode 7 (remote controller
always permitted)
Same as mode 5
Same as mode 6
PACD011001C2
Input B (between B2~Bc)
Stops by ON, remote controller
inhibited Disregard input A Input
A permitted by OFF
"Stops by ON, remote controller
inhibited Remote controller
permitted by OFF
Stops by ON
Inhibited by ON (remote
controller inhibited)
Same as mode 7
Remote controller inhibited by
ON
Same as mode 7
Forced OFF by thermostat by
ON
Room temperature shift
operation by ON
Forced OFF by thermostat by
ON
Room temperature shift
operation by ON
Appendix

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents