Low Noise / Demand Operation (Mx1 Series) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

Test Operation
1.11
Low Noise / Demand Operation
BMS interface adaptor for outdoor unit is required for each low noise and demand control zone.
„ By using a separate BMS interface adaptor for outdoor unit and setting the outdoor unit address (setting
„ Outdoor unit address setting (Setting mode 2; see page 69.)
„ BMS interface adaptor for outdoor unit address setting
‹ Decide and set demand address 0 - 31 for each demand and low noise control zone. (See fig. below.)
‹ Set SS1 to "BOTH" (factory set) or "C / H."
94
mode 2) for each low noise and demand control zone, demand and low noise operation is carried out in
accordance with contact input received from the adaptor in each zone.
¡
llllll
Demand address
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 0
(MX1 Series)
¡
lllll
Demand address
F1 / F2
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 1
Test Operation Urban Multi "MX1, ME1 Series" Using R-22
PACD011001C2
¡
¡
Demand address
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 2
¡
llll
l
F1 / F2
(VL030)