Panasonic Urban Multi MX1R Series Service Manual page 126

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
Example of System
Using Wireless
Remote Controller
For control by two remote controllers, be sure to designate the indoor unit remote controller as the master.
The only combination that can't be used is two wireless remote controllers. Transmission wiring between
the separately installed receiver unit and indoor unit can be up to 200 meters long.
Comparison of
Functions of Wired
Function /display
and Wireless
Operation lamp
Remote Controllers
ON/OFF
Operation mode selection
Air flow direction setting
Filter sign reset
Display "time to clean air
cleaner element" Filter sign
display
Display "ventilation/cleaning"
Defrost hot start
Display "under centralised
control"
Display "changeover under
control"
Thermostat sensor in remote
controller
Ventilation mode
„ All operation buttons (preset temperature, fan speed, timer, inspection / test operation, cool/heat
Test Operation Urban Multi "MX1, ME1 Series" Using R-22
selection permission and group No. setting for centralised control) function in the same manner.
Wired remote controller
Remote controller LED
Toggles between on and off each time the button is pushed.
Selects operation mode. Cool/heat
mode cannot be switched during
changeover under control.
The air flow direction is set by adjusting
with the air flow direction adjustment
button while viewing setting position in
the liquid crystal display.
Resets the filter and element cleaning
display.
Remote controller LCD display
Displayed when air cleaner unit is
connected.
Displays defrost and hot start.
Displayed during centralised control.
Displayed when cool/heat mode
cannot be switched.
Equipped
Equipped
Test Operation
Wireless remote controller
Receiver unit LED
Selects operation mode. Cool/heat
display switches during changeover
under control.
The air flow direction is set by adjusting
with the air flow direction adjustment
button while viewing the position of the
louver.
Resets the filter and element cleaning
display. Displayed by optical sensor
LED.
Displayed by receiver unit LED.
Ventilation/cleaning displayed by
receiver unit LED.
Displayed by receiver unit LED.
Not displayed, but you are warned by a
buzzer sound emitted from the
receiver unit .
Not displayed (you are warned by a
buzzer sound when the mode cannot
be switched).
Not equipped
Not equipped
105