Me1R Series (Heat Recovery) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

Outline
2.2

ME1R Series (Heat Recovery)

„ Allows individual control of different types of indoor units with varying capacities totaling 50 to 130% of
„ Indoor units ranging from the smallest 20 type (0.8 HP).
„ Flexible refrigerant piping: equivalent length of 125 m, actual length of 100 m, outdoor unit height
∗ Outside temperature of 35°C for operation mode (A), 0°C for operation mode (D), and typical seasonal
outside temperatures for others.
222
the outdoor unit capacity.
∗ When total indoor capacity exceeds 100%, indoor unit operating capacity may decrease slightly if all
indoor units are operated at the same time.
difference of 50 m, and height difference of 15 m between indoor units.
CU-10ME
(10HP)
Outdoor unit
(A) All units in cooling operation
Heat radiation
(B) Most units in cooling operation. and a few units in heating operation
Heat radiation
(C) Most units in heating operation, and a few units in cooling operation
Heat absorption
(D) All units in heating operation
Heat absorption
General Information Urban Multi "MX1R, ME1R Series" Using R-407C
System outline & operation mode
2.5 HP or
2.5 HP or
equivalent
equivalent
No. 1
No. 2
Indoor unit
Cooling
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
PACD011001C2
HR box
2.5 HP or
2.5 HP or
equivalent
equivalent
No. 3
No. 4
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
(M004)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents