Compressor Capacity Control - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
1.17

Compressor Capacity Control

CU-5
Pressure is sampled every 20 seconds by pressure sensor, and the inverter compressor is controlled in 13
stages by microcomputer.
Frequency range: 34 - 116 Hz (13 stages) and common for 50/60Hz area.
CU-8·10
Pressure is sampled every 20 seconds by two pressure sensors, and the inverter compressor is controlled
in 20 stages by microcomputer.
Function Urban Multi "MX1, ME1 Series" Using R-22
Min. output
Frequency
30Hz
34Hz
38Hz
42Hz
48Hz
54Hz
60Hz
68Hz
76Hz
86Hz
96Hz
106Hz
116Hz
Max. output
(VE004)
Commercial power supply
compressor (off)
Frequency
30Hz+OFF
34Hz+OFF
38Hz+OFF
42Hz+OFF
48Hz+OFF
54Hz+OFF
60Hz+OFF
68Hz+OFF
76Hz+OFF
86Hz+OFF
96Hz+OFF
106Hz+OFF
Commercial power supply
compressor (full load)
Frequency
38Hz+ON
48Hz+ON
60Hz+ON
76Hz+ON
86Hz+ON
96Hz+ON
106Hz+ON
116Hz+ON
Function
Min. output
Max. output
(VE006)
49