Function
Operation Contents
Upper Limit Frequency
Limited to 38Hz + ON
250
Step 1 → Discharge defrost
Compressor
1 Minute
Elapses
EEV
Preparation
for Defrost
Outdoor Unit Fan
Outdoor Unit Heat Exchanger
4 Way Valve
(VF015)
Injection 1
Injection 2
Hot Gas
Step 2 → Suction defrost
Compressor
EEV
Outdoor Unit Fan
Outdoor Unit Heat Exchanger
4 Way Valve
Injection 1
Injection 2
Hot Gas
Step 3 → HR solenoid valve changeover
Compressor
EEV
Outdoor Unit Fan
Outdoor Unit Heat Exchanger
4 Way Valve
Injection 1
Injection 2
Hot Gas
Step 4 → Refrigerant is discharged from accumulator
Compressor
EEV
Outdoor Unit Fan
Outdoor Unit Heat Exchanger
4 Way Valve
Injection 1
Injection 2
Hot Gas
Td Protection Control
3 Minutes Elapsed
Td Protection Control
Td Protection Control
Conclution of Defrost Completion
Condition
All of R2-1T, R2-2T ≥ 9.5ºC
or 
Pc > 22k
10 Minutes Elapsed Since
Defrost Operation Start
Td Protection Control
40 Seconds Elapsed
Limit of EV Opening
Td Protection Control
Low Pressure Protection Control
5 Minutes Elapsed
or 
Pc > 15.2k
R5T > Te + 10ºC
Normal Control
∗Pc = Condensing Pressure
Function Urban Multi "MX1R, ME1R Series" Using R-407C
PACD011001C2
k = kg/cm²
86Hz + OFF
2000pls
OFF + OFF
Condenser
OFF
OFF
ON
86Hz + ON
2000pls
OFF + OFF
Condenser
OFF
ON
38Hz + OFF
2000pls
OFF + OFF
Condenser
OFF
OFF
ON
76Hz + OFF
H + ON
Evaporator
ON
OFF