Outdoor Unit: Malfunction Of Discharge Pipe Thermistor (R3T) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
3.20 Outdoor Unit:
J3
Remote Controller
Display
„ Defect of thermistor (R3-1(11)T, R3-2(12)T or R3-13T) for outdoor unit discharge pipe
Supposed Causes
„ Defect of outdoor unit PC board (A1P)
Troubleshooting
The alarm indicator is displayed when the fan is being used also.
Note:
16~20 HP class ··· R3-1T, R3-2T (A1P)
24~30 HP class ··· R3-11T, R3-12T (A1P), R3-13T (A3P)
Troubleshooting UM Combination "MA1R Series" Using R-407C
Malfunction of Discharge Pipe Thermistor (R3T)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X16A,
NO
X17A or X21Aof outdoor unit
PC board
(A1P or A3P).
YES
Resistance
is normal when
measured after
NO
disconnecting the thermistor
(R3-1(11)T, R3-2(12)T or
R3-13T) from the indoor
unit PC board.
(3.5kΩ~
400kΩ)
YES
Troubleshooting
Connect the thermistor and turn on
again.
Replace the thermistor (R3-1(11)T, R3-
2(12)T, or R3-13T).
Replace outdoor unit PC board A1P or
A3P.
(VF046)
517

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents