Malfunction of Transmission between Optional Controllers for Centralised
Control
M8 M8 M8 M8
Remote Controller
Display

„ Malfunction of transmission between optional controllers for centralised control

Supposed Causes
„ Defect of PC board of optional controllers for centralised control
Troubleshooting
Troubleshooting Urban Multi "MX1, ME1 Series" Using R-22
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has a
once connected
optional controller for
YES
centralised control been
disconnected or
its address
changed?
NO
Is
the power supply
NO
turned on for all optional
controllers for centralised
control?
YES
Is
the reset switch
NO
of all optional controllers for
centralised control
set to "normal"?
YES
Is
transmission wiring
YES
disconnected or wired
incorrectly?
NO
Troubleshooting (OP: Schedule Timer)
Reset power supply simultaneously for
all optional controllers for centralised
control.
Turn on power supply for all optional
controllers for centralised control.
Set reset switch to "normal".
Fix the wiring correctly.
The PC board of one of the optional
controllers for centralised control is
defective. Try turning on/off using each
optional controllers for centralised
control, and replace the PC board of
the one that is unable to control the
indoor unit.
(VF076)