Allowed Range Of Indoor Unit And Hr Box Connection - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
2.3

Allowed Range of Indoor Unit and HR Box Connection

Range A
Range B
HR box
Range C
Indoor unit
„ Arrange systems to conform below conditions referring to above diagram.
Range
Range A Total indoor unit capacity
Range B Total indoor unit capacity
Range C Total indoor unit capacity
General Information Urban Multi "MX1R, ME1R Series" Using R-407C
Item
allowed for simultaneous
cooling/heating operations
allowed for connection to HR box
Range C
Range C
Range C
Model of outdoor
Total capacity of
unit and HR box
connectable indoor
units
CU-8ME1XPK
11.2 to 29.1kW
CU-10ME1XPK
14 to 36.4kW
CU-8ME1XPK
11.2kW or more
CU-10ME1XPK
14kW or more
CZ-100HR1HP
less than 11.2kW
CZ-160HR1HP
11.2 to 18kW
Outline
( Cooling
( Cooling
only unit )
only unit )
(M005)
Max. number of
connectable indoor
units
13 units
16 units
13 units
16 units
5 units or less
6 units or less
223