Panasonic Urban Multi MX1R Series Service Manual page 280

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
Low Outdoor Air
Cooling in
Conditions (Step 2)
Function Urban Multi "MX1R, ME1R Series" Using R-407C
Normal operation
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 8.0 kg/cm²
(0.784 MPa)
&
• Radiator fin temperature < 67˚C
Conditions satisfied
• Compressor off
• Other than cooling (includes oil return)
• High pressure > 17.3 kg/cm²
• Radiator fin temperature > 87˚C
Conditions satisfied
Function
or
or
(1.690 MPa)
or
Step 2
(M018)
259