Panasonic Urban Multi MX1R Series Service Manual page 67

Using r-407c / r-22
Table of Contents

Advertisement

Function
Low Outdoor Air
Cooling in
Conditions (Step 2)
46
Normal operation
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 7.5 kg/cm²
(0.735 MPa)
&
• Radiator fin temperature < 60˚C
Conditions satisfied
• Compressor off
• Other than cooling (includes oil return)
• High pressure > 15.8 kg/cm²
• Radiator fin temperature > 80˚C
Conditions satisfied
Function Urban Multi "MX1, ME1 Series" Using R-22
PACD011001C2
or
or
(1.548 MPa)
or
Step 2
(VF007-2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents