Panasonic Urban Multi MX1R Series Service Manual page 450

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
„ When condition (Th6 – Te < 5) remains for 3 continuous minutes in steps higher than step 1-2, EVs of
„ From 24 HP model or higher, the fan (M12F) on the inverter box side stops if operating at fan tap (3) or
„ In this control, the compressor load increase based on PI calculation is conducted once every 2
∗ Tfin: Inverter fin temperature.
3.1.5
Compressor Capacity Control
INV Compressor Operating Frequency
The operating frequency changes in the following steps.
„ PA-16·18·20MA
Function UM Combination "MA1R Series" Using R-407C
all indoor units in thermostat-OFF status are set to 200 pls. This is canceled when Th6 – Te > 15. (for
prevention of wet operation in cooling operation when outside temperature is low)
Th6 – Te: Suction pipe temperature – Evaporation temperature
lower. Therefore, Tfin switches M11F OFF and M12F ON.
®­ ¬
M11F : H / L / OFF
M12F : OFF
minutes. The load decrease operation is conducted once every 20 minutes.
Frequency
NO.
INV
STD
1
29Hz
OFF
2
31Hz
OFF
3
33Hz
OFF
4
35Hz
OFF
5
37Hz
OFF
6
39Hz
OFF
7
41Hz
OFF
8
43Hz
OFF
9
46Hz
OFF
10
48Hz
OFF
11
52Hz
OFF
12
55Hz
OFF
13
58Hz
OFF
14
62Hz
OFF
15
64Hz
OFF
16
67Hz
OFF
17
71Hz
OFF
18
75Hz
OFF
19
37Hz
ON
20
41Hz
ON
21
46Hz
ON
22
52Hz
ON
23
58Hz
ON
24
64Hz
ON
25
71Hz
ON
26
79Hz
ON
T fin > 87˚C
O
T fin < 67˚C
„ PA-24~30MA
Frequency
NO.
INV
STD1
1
29Hz
OFF
2
31Hz
OFF
3
33Hz
OFF
4
35Hz
OFF
5
37Hz
OFF
6
39Hz
OFF
7
41Hz
OFF
8
43Hz
OFF
9
46Hz
OFF
10
48Hz
OFF
11
52Hz
OFF
12
55Hz
OFF
13
58Hz
OFF
14
62Hz
OFF
15
64Hz
OFF
16
67Hz
OFF
17
71Hz
OFF
18
75Hz
OFF
19
37Hz
ON
20
41Hz
ON
21
46Hz
ON
22
52Hz
ON
23
58Hz
ON
24
64Hz
ON
25
71Hz
ON
26
41Hz
ON
27
52Hz
ON
28
64Hz
ON
29
79Hz
ON
Outline of Control
M11F : OFF
M12F : ON
(V0820)
STD2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
429