Low Pressure Drop Due to Refrigerant Shortage or Electronic Expansion
Valve Failure
U0 U0 U0 U0
Remote Controller
Display
„ Refrigerant shortage or refrigerant system clogging (incorrect piping)
Supposed Causes
„ Defect of pressure sensor
„ Defect of outdoor unit PC board
Troubleshooting
Troubleshooting Urban Multi "MX1R, ME1R Series" Using R-407C
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
YES
Cooling
NO
The suction
pipe temperature minus
coil temperature is 20 ˚C
or higher.
NO
Resistance
is normal when
measured with the
suction pipe thermistor (R4T
or R4-1T, R4-2T) and coil
thermistor (R2T or R2-1T,
R2-2T) disconnected
from the outdoor
unit PC
board.
YES
Low pressure
is 1.0 kg/cm² (0.098 MPa) or
less.
NO
The voltage
of X21A pins (2)
and (3) on both sides of
outdoor unit PC board (A1P) is
0.8 VDC or less.
(Pressure sensor
output
voltage)
NO
YES
NO
Troubleshooting
YES
Refrigerant shortage or refrigerant
system is clogged. Requires check
of refrigerant system.
YES
Replace outdoor unit PC board.
Replace pressure sensor.
Refrigerant shortage or refrigerant
system is clogged. Requires
check of refrigerant system.
Replace the thermistor.
Replace the outdoor unit PC
board.