Functional Diagrams For Condition Monitoring - ABB RELION 615 Series Applications Manual

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
3.7.3.3
IN
CB1_POSITION_CLOSE
TRPPTRC1_86_94-1_TRIP
IN
CB2_POSITION_CLOSE
GUID-9DCED52D-3641-451C-9C16-A9FCE08F4CDE V1 EN
Figure 239:
Trip circuit monitoring
REF615 ANSI
Application Manual

Functional diagrams for condition monitoring

Two trip circuit monitoring stages TCSSCBR1_TCM-1 and TCSSCBR2_TCM-2 are
provided to supervise the trip circuit of the circuit breaker connected at PO3 (X100:15-19)
and PO4 (X100:20-24).
NOT
OUT
O:82|T:2.5|I:0
B1
B2
NOT
OUT
O:45|T:2.5|I:1
B1
B2
TRPPTRC2_86_94-2_TRIP
The TCSSCBR1_TCM-1 and TCSSCBR2_TCM-2 functions are blocked by
TRPPTRC1_86/94-1, TRPPTRC2_86/94-2 and when the circuit-breaker is not in closed
position.
By default it is expected that there is no external resistor in the circuit
breaker tripping/closing coil circuit connected parallel with circuit
breaker normally open/closed auxiliary contact.
The circuit breaker condition monitoring function SSCBR1_52CM supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision alarms.
REF615 standard configurations
OR
TCSSCBR1
O
BLOCK
O:87|T:5|I:1
O:84|T:2.5|I:3
OR
O
BLOCK
O:49|T:2.5|I:5
ALARM
TCSSCBR1_TCM1_ALARM
TCSSCBR2
ALARM
TCSSCBR2_TCM2_ALARM
O:52|T:5|I:2
Section 3