SEQSPVC1_60-1_FUSEF_U
SEQSPVC1_60-1_FUSEF_U
ROVPTOV1_59G_TRIP
ROVPTOV2_59N-1_TRIP
ROVPTOV3_59N-2_TRIP
GUID-BF21470C-A5D6-4B50-9955-F9BF3A43FD7A V1 EN
Figure 128:
Residual voltage protection function
The MSVPR1_27R-1 function is used to monitor the remanent voltage over a decaying
frequency after power supply is lost, before allowing connection of backup power. It
provides a permissive signal indicating when connecting of backup power can be
completed safely.
GUID-58186369-0E59-4DFB-B73E-4A5DC4A62FF4 V1 EN
Figure 129:
Three-phase remnant undervoltage protection function
General pickup and trip signals from all functions are connected to minimum pulse timer
TPGAPC1 for setting the minimum pulse length for the outputs. The output from
TPGAPC1 can be connected to binary outputs. However, these are not connected in the
configuration.
If a new protection function block is added to the configuration, check the
activation logic and add connections.
REF615 standard configurations
ROVPTOV1
BLOCK
TRIP
PICKUP
O:50|T:5|I:1
ROVPTOV2
BLOCK
TRIP
PICKUP
O:46|T:5|I:2
ROVPTOV3
BLOCK
TRIP
PICKUP
O:48|T:5|I:3
OR6
B1
O
B2
B3
B4
B5
B6
O:116|T:2.5|I:60
MSVPR1
BLOCK
U_LOW
O:94|T:2.5|I:1
Section 3
ROVPTOV1_59G_TRIP
ROVPTOV1_59G_PICKUP
ROVPTOV2_59N-1_TRIP
ROVPTOV2_59N-1_PICKUP
ROVPTOV3_59N-2_TRIP
ROVPTOV3_59N-2_PICKUP
ROVPTOV_TRIP
MSVPR1_27R-1_U_LOW
117