Functional Diagrams For Protection - ABB RELION 615 Series Applications Manual

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
3.5.3.1
REF615 ANSI
Application Manual
The analog channels have fixed connections to the different function blocks inside the
protection relay's standard configuration. However, the 12 analog channels available for
the disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The phase currents to the protection relay are fed from Rogowski or Combi sensors. The
residual current to the protection relay is fed from either residually connected CTs, an
external core balance CT, neutral CT or calculated internally.
The phase voltages to the protection relay are fed from Combi sensors. The residual
voltage is calculated internally.
The signal marked with IA, IB and IC represents the three phase currents. The signal IG
represents the measured ground current.
The signal marked with VA, VB and VC represents the three phase voltages.
The protection relay offers six different setting groups which can be set based on
individual needs. Each group can be activated or deactivated using the setting group
settings available in the protection relay.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.

Functional diagrams for protection

The functional diagrams describe the relay's protection functionality in detail and
according to the factory set default connections.
Five overcurrent stages are offered for overcurrent and short-circuit protection. Three of
them include directional functionality DPHxPDOC_5xP-1/2.
REF615 standard configurations
Section 3
105

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ref615 ansi

Table of Contents