Functional Diagrams - ABB RELION 615 Series Applications Manual

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.4.3
72
Channel
ID text
55
-
56
-
57
-
58
-
59
-
60
-
61
-
62
-
63
-
64
-

Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-
function connections. The default connections can be viewed and changed with PCM600
according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
protection relay's standard configuration. However, the 12 analog channels available for
the disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The phase currents to the protection relay are fed from a current transformer. The residual
current to the protection relay is fed from either residually connected CTs, an external core
balance CT, neutral CT or calculated internally.
The signal marked with IA, IB and IC represents the three phase currents. The signal IG
represents the measured ground current.
The signal marked with VA, VB and VC represents the three phase voltages. The signal
VG represents the measured ground voltage.
The protection relay offers six different setting groups which can be set based on
individual needs. Each group can be activated or deactivated using the setting group
settings available in the protection relay.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
1MAC109016-MB C
Level trigger mode
-
-
-
-
-
-
-
-
-
-
REF615 ANSI
Application Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ref615 ansi

Table of Contents