Section 3
REF615 standard configurations
3.6.3.4
156
TRPPTRC1_86/94-1_TRIP
TRPPTRC2_86/94-2_TRIP
X120_BI3_CB_OPEN
GUID-AB98D2B8-4D4A-4293-A333-094BFEDD198C V1 EN
Figure 198:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
can be activated using the configuration logic, which is based on the status of the trip
logics. However, other signals can be connected based on the application needs.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position. SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the circuit breaker truck is
closed in service position.
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_52-1_ENA_CLOSE
FALSE
CBXCBR1_52-1_BLK_CLOSE
CBXCBR1_52-1_AU_OPEN
CBXCBR1_52-1_AU_CLOSE
GUID-11BD5557-CD74-4A83-9895-EB63C6FDEF0A V1 EN
Figure 199:
Circuit breaker control logic: Circuit breaker 1
CBXCBR1_52-1_EXE_CL
DARREC1_79_CLOSE_CB
GUID-056B2A01-7F96-4035-9DBE-F6935F8EBF19 V1 EN
Figure 200:
Circuit breaker control logic: Signals for the closing coil of circuit breaker
1
OR6
B1
O
B2
B3
B4
B5
B6
O:107|T:2.5|I:19
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
O:74|T:5|I:1
OR
B1
O
B2
O:82|T:2.5|I:10
1MAC109016-MB C
TCSSCBR_BLOCKING
CBXCBR1_52-1_SELECTED
CBXCBR1_52-1_EXE_OP
CBXCBR1_52-1_EXE_CL
CB_CLOSE_COMMAND
REF615 ANSI
Application Manual