protection in compensated networks. The binary input X110:BI2 is intended for
controlling directional ground-fault protection blocks' relay characteristic angle (RCA:
0°, -90°) or operation mode (IoSinφ, IoCosφ) change. The same input is also available for
wattmetric protection.
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_FAIL
DEFLPDEF1_67/51N-1_TRIP
DEFLPDEF2_67/51N-2_TRIP
DEFHPDEF1_67/50N-1_TRIP
DEFHPDEF2_67/50N-2_TRIP
GUID-E70FF7C3-5F0C-42B7-95A4-03F5BAC401ED V1 EN
Figure 172:
Directional ground-fault protection function
GUID-CEA9A04E-6E6B-4849-9989-619E68D65067 V1 EN
Figure 173:
Non-directional ground-fault protection
REF615 standard configurations
DEFLPDEF1
BLOCK
TRIP
ENA_MULT
PICKUP
RCA_CTL
O:46|T:5|I:1
DEFLPDEF2
BLOCK
TRIP
ENA_MULT
PICKUP
RCA_CTL
O:19|T:5|I:2
DEFHPDEF1
BLOCK
TRIP
ENA_MULT
PICKUP
RCA_CTL
O:18|T:5|I:1
DEFHPDEF2
BLOCK
TRIP
ENA_MULT
PICKUP
RCA_CTL
O:12|T:5|I:2
OR6
B1
O
B2
B3
B4
B5
B6
O:115|T:2.5|I:55
EFHPTOC1
BLOCK
TRIP
ENA_MULT
PICKUP
O:13|T:5|I:1
Section 3
DEFLPDEF1_67/51N-1_TRIP
DEFLPDEF1_67/51N-1_PICKUP
DEFLPDEF2_67/51N-2_TRIP
DEFLPDEF2_67/51N-2_PICKUP
DEFHPDEF1_67/50N-1_TRIP
DEFHPDEF1_67/50N-1_PICKUP
DEFHPDEF2_67/50N-2_TRIP
DEFHPDEF2_67/50N-2_PICKUP
DEFxPDEF_TRIP
EFHPTOC1_50G-1_TRIP
EFHPTOC1_50G-1_PICKUP
141