ABB RELION 615 Series Applications Manual page 85

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
REF615 ANSI
Application Manual
ARCSARC1_AFD-1_TRIP
ARCSARC2_AFD-2_TRIP
ARCSARC3_AFD-3_TRIP
GUID-834F0CCE-C98A-4EBF-82D1-E33A3F5C4111 V1 EN
Figure 65:
Arc protection
The optional autoreclosing function is configured to be initiated by trip signals from a
number of protection stages through the INIT_1...5 inputs. It is possible to create
individual autoreclose sequences for each input.
The autoreclosing function can be inhibited with the INHIBIT_RECL input. By default,
few selected protection function operations are connected to this input. A control
command to the circuit breaker, either local or remote, also blocks the autoreclosing
function via the CBXCBR1_52-1_SELECTED signal.
The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY input in DARREC1_79. This signal is not connected in the configuration.
The open command from the autorecloser is connected directly to binary output
X100:PO3, whereas the close command is connected directly to binary output X100:PO1.
Set the parameters for DARREC1_79 properly.
REF615 standard configurations
ARCSARC1
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:15|T:2.5|I:11
ARCSARC2
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:13|T:2.5|I:21
ARCSARC3
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:18|T:2.5|I:31
OR6
B1
O
B2
B3
B4
B5
B6
O:154|T:2.5|I:61
Section 3
ARCSARC1_AFD-1_TRIP
ARCSARC1_AFD-1_ARC_FLT_DET
ARCSARC2_AFD-2_TRIP
ARCSARC2_AFD-2_ARC_FLT_DET
ARCSARC3_AFD-3_TRIP
ARCSARC3_AFD-3_ARC_FLT_DET
ARCSARC_TRIP
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ref615 ansi

Table of Contents