ABB RELION 615 Series Applications Manual page 132

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
CONTROL_LOCAL
FALSE
CONTROL_REMOTE
FALSE
GUID-948D9F09-FBDB-424E-9469-FA28C2AD223D V1 EN
Figure 147:
External closing command for circuit breaker
126
T1PTTR1_49F_BLK_CLOSE
GUID-D770B4AE-D735-42F2-B34A-1FC5366F4E63 V1 EN
Figure 146:
Circuit breaker close blocking logic
The configuration includes the logic for generating circuit breaker external closing and
opening command with the relay in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect the additional signal for closing and opening of circuit breaker in
local or remote mode if applicable for the configuration.
AND
B1
O
B2
O:70|T:2.5|I:1
AND
B1
O
B2
O:71|T:2.5|I:0
B1
CONTROL_LOCAL
B2
FALSE
B1
CONTROL_REMOTE
B2
FALSE
GUID-A36678F4-2A9B-4423-9971-F9EEF74E1602 V1 EN
Figure 148:
External opening command for circuit breaker
OR6
B1
O
B2
B3
B4
B5
B6
O:74|T:2.5|I:17
OR
B1
B2
O:77|T:2.5|I:7
AND
O
O:68|T:2.5|I:3
B1
B2
AND
O:75|T:2.5|I:9
O
O:69|T:2.5|I:2
1MAC109016-MB C
CBXCBR1_52-1_BLK_CLOSE
O
CBXCBR1_52-1_AU_CLOSE
OR
O
CBXCBR1_52-1_AU_OPEN
Application Manual
REF615 ANSI