ABB RELION 615 Series Applications Manual page 113

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
REF615 ANSI
Application Manual
DPHLPDOC2_67/51P-2_PICKUP
GUID-ED03DF9D-6486-4D57-81B2-C7CFCCB7FC31 V1 EN
Figure 111:
Upstream blocking logic
The output BLK2H of three-phase inrush detector INRPHAR1_INR-1 enables either
blocking the function or multiplying the active settings for any of the available
overcurrent or ground-fault function blocks.
GUID-877B89DE-CBF8-4976-8121-4F5AAB01111B V1 EN
Figure 112:
Inrush detector function
Two negative-sequence overcurrent protection stages NSPTOC1_46-1 and
NSPTOC2_46-2 are provided for phase unbalance protection. These functions are used to
protect the feeder against phase unbalance. Both the negative-sequence overcurrent
protections are blocked in case of detection in failure in secondary circuit of current
transformer.
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_FAIL
GUID-CB92D4CF-F779-45BE-A753-26A71FBF9556 V1 EN
Figure 113:
Negative-sequence overcurrent protection function
Four stages are provided for non-directional ground-fault protection EFHPTOC1....
4_50G-1/2, 50N-1/2. Three stages are provided for directional ground-fault protection.
According to the relay's order code, the directional ground-fault protection method can be
based on conventional directional ground-fault DEFxPDEF_67/51N-1/2, 67/50N-1/2,
only or alternatively used together with admittance-based ground-fault protection
EFPADM_21YN or wattmetric-based ground-fault protection WPWDE_32N. A
dedicated protection stage INTRPTEF_67NIEF is used either for transient-based ground-
fault protection or for cable intermittent ground-fault protection in compensated
networks.
REF615 standard configurations
OR6
B1
O
B2
B3
B4
B5
B6
O:151|T:2.5|I:65
INRPHAR1
BLOCK
BLK2H
O:107|T:2.5|I:1
NSPTOC1
NSPTOC1
BLOCK
BLOCK
TRIP
TRIP
ENA_MULT
ENA_MULT
PICKUP
PICKUP
O:24|T:5|I:1
O:54|T:5|I:1
NSPTOC2
NSPTOC2
BLOCK
BLOCK
TRIP
TRIP
ENA_MULT
ENA_MULT
PICKUP
PICKUP
O:25|T:5|I:2
O:55|T:5|I:2
Section 3
UPSTEAM_OC_BLOCKING
INRPHAR1_INR-1_BLK2H
NSPTOC1_46-1_TRIP
NSPTOC1_46-1_TRIP
NSPTOC1_46-1_PICKUP
NSPTOC1_46-1_PICKUP
NSPTOC2_46-2_TRIP
NSPTOC2_46-2_TRIP
NSPTOC2_46-2_PICKUP
NSPTOC2_46-2_PICKUP