ABB Relion 615 Series List Manual

Feeder protection and control
Hide thumbs Also See for Relion 615 Series:

Advertisement

Quick Links

®
Relion
615 series
Feeder Protection and Control
REF615
IEC 60870-5-103 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion 615 series Feeder Protection and Control REF615 IEC 60870-5-103 Point List Manual...
  • Page 3 Document ID: 1MRS756712 Issued: 2010-06-11 Revision: C Product version: 3.0 © Copyright 2010 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............3 This manual..................3 Intended audience................3 Product documentation...............4 Product documentation set............4 Document revision history.............5 Related documentation..............6 Symbols and conventions..............6 Safety indication symbols..............6 Manual conventions...............6 Functions, codes and symbols............7 Section 2 IEC 60870-5-103 data mappings........11 Overview...................11 Point list for REF615 Ver.
  • Page 8 Table of contents Basic application functions............30 Miscellaneous................30 Section 4 Glossary.................31 REF615 Point List Manual...
  • Page 9: Section 1 Introduction

    Section 1 1MRS756712 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 10: Product Documentation

    Section 1 1MRS756712 C Introduction Product documentation 1.3.1 Product documentation set Engineering manual Engineering manual Engineering manual Installation manual Installation manual Installation manual Commissioning manual Commissioning manual Commissioning manual Operation manual Operation manual Operation manual Service manual Service manual Service manual Application manual Application manual Application manual...
  • Page 11: Document Revision History

    Some of the manuals are not available yet. 1.3.2 Document revision history Document revision/date Product version History A/2009-03-04 First release B/2009-07-03 Content updated C/2010-06-11 Content updated to correspond to the product version Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. REF615 Point List Manual...
  • Page 12: Related Documentation

    Section 1 1MRS756712 C Introduction 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual 1MRS756710 Symbols and conventions 1.4.1 Safety indication symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 13: Functions, Codes And Symbols

    Section 1 1MRS756712 C Introduction The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font, for example: When the function starts, the START output is set to TRUE. 1.4.3 Functions, codes and symbols Table 1: REF615 Functions, codes and symbols...
  • Page 14 Section 1 1MRS756712 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Transient / intermittent earth-fault INTRPTEF1 Io> -> IEF 67NIEF protection Non-directional (cross-country) earth EFHPTOC1 Io>> (1) 51N-2 (1) fault protection, using calculated Io Negative-sequence overcurrent NSPTOC1 I2> (1) 46 (1) protection, instance 1 Negative-sequence overcurrent NSPTOC2...
  • Page 15 Section 1 1MRS756712 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Disconnector position indication, DCSXSWI1 I <-> O DC (1) I <-> O DC (1) instance 1 Disconnector position indication, DCSXSWI2 I <-> O DC (2) I <-> O DC (2) instance 2 Disconnector position indication, DCSXSWI3...
  • Page 17: Section 2 Iec 60870-5-103 Data Mappings

    Section 2 1MRS756712 C IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview These tables show the default point definitions. The user is able to freely remap all these data. In that case PCM600 can provide an updated point list export of the new outlook.
  • Page 18 Section 2 1MRS756712 C IEC 60870-5-103 data mappings Frame No6 Shows if the value is present in Class2 frame 6. Frame No7 Shows if the value is present in Class2 frame 7. Comment Additional information. REF615 Point List Manual...
  • Page 19: Point List For Ref615 Ver. 3.0 Fe01-08

    Section 2 1MRS756712 C IEC 60870-5-103 data mappings Point list for REF615 Ver. 3.0 FE01-08 REF615 Point List Manual...
  • Page 20 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 21 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 22 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 23 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 24 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 25 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 26 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 27 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 28 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 29 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 30 Section 2 1MRS756712 C IEC 60870-5-103 data mappings REF615 Point List Manual...
  • Page 31: Section 3 Interoperability Profile For 615 Series Iec 60870-5-103

    Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 Section 3 Interoperability profile for 615 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard.
  • Page 32: Application Layer

    Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
  • Page 33: Supervision Indications In Monitor Direction

    Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
  • Page 34: Auto-Reclosure Indications In Monitor Direction

    Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
  • Page 35: Measurands In Monitor Direction

    Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I , P, Q, f L1,2,3 L1,2,3...
  • Page 36 Section 3 1MRS756712 C Interoperability profile for 615 series IEC 60870-5-103 3.3.5 Basic application functions ⃞ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in 615 series devices is 2.4.
  • Page 37 Section 4 1MRS756712 C Glossary Section 4 Glossary Application function block library Autoreclosing ASDU Application-layer service data unit Circuit breaker Double point information Disturbance recorder Electromagnetic compatibility Default function type General interrogation Human-machine interface Input/output International Electrotechnical Commission IEC 60870-5-103 Communication standard for protective equipment; A serial master/slave protocol for point-to-point communication IEC 61850...
  • Page 40 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...