1MAC109016-MB C
REF615 ANSI
Application Manual
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_52-1_ENA_CLOSE
FALSE
CBXCBR1_52-1_BLK_CLOSE
CBXCBR1_52-1_AU_OPEN
CBXCBR1_52-1_AU_CLOSE
GUID-F0EE29F3-8214-4968-97C0-A0B5C4531D24 V1 EN
Figure 83:
Circuit breaker control logic: Circuit breaker 1
CBXCBR1_52-1_EXE_CL
DARREC1_79_CLOSE_CB
GUID-CC488E8F-AD35-4514-9168-960BF7A8C8C2 V1 EN
Figure 84:
Circuit breaker control logic: Signals for the closing coil of circuit breaker
1
CBXCBR1_52-1_EXE_OP
TRPPTRC1_86/94-1_TRIP
DARREC1_79_OPEN_CB
GUID-1B47925D-F420-4804-999B-35E9D60345CD V1 EN
Figure 85:
Circuit breaker control logic: Signals for the opening coil of circuit breaker
1
IN
TRPPTRC1_86/94-1_TRIP
IN
TRPPTRC2_86/94-2_TRIP
GUID-CDD7F80B-97EC-44FB-AF4A-E84E3FDBA84E V1 EN
Figure 86:
Circuit breaker close enable logic
The configuration includes the logic for generating circuit breaker external closing and
opening command with the relay in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
REF615 standard configurations
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
O:81|T:5|I:1
OR
B1
O
B2
O:89|T:2.5|I:11
OR6
B1
O
B2
B3
B4
B5
B6
O:88|T:2.5|I:22
NOT
OUT
B1
B2
O:76|T:2.5|I:1
B3
B4
B5
B6
NOT
O:80|T:2.5|I:0
OUT
O:75|T:2.5|I:2
Section 3
CBXCBR1_52-1_SELECTED
CBXCBR1_52-1_EXE_OP
CBXCBR1_52-1_EXE_CL
CB_CLOSE_COMMAND
CB_OPEN_COMMAND
AND6
O
CBXCBR1_52-1_ENA_CLOSE