Default Disturbance Recorder Settings - ABB RELION 615 Series Applications Manual

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.7.2.2
168

Default disturbance recorder settings

Table 37:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
U1
6
U2
7
U3
8
U1B
9
U2B
10
U3B
11
-
12
-
Table 38:
Default disturbance recorder binary channels
Channel
ID text
1
TRPPTRC1_86/94-1_TRIP
2
TRPPTRC2_86/94-2_TRIP
3
CBXCBR1_52-1_EXE_OP
4
CBXCBR1_52-1_EXE_CL
5
CBXCBR2_52-2_EXE_OP
6
CBXCBR2_52-2_EXE_CL
7
CCBRBRF1_50BF-1_TRBU
8
CCBRBRF1_50BF-2_TRBU
9
ARCSARC1 - ARC flt det
10
ARCSARC2 - ARC flt det
11
ARCSARC3 - ARC flt det
12
OC(1)_PICKUP_ALARM
13
PHPTUC1_37-1_TRIP
14
PHPTOV2_59-2_TRIP
15
REMPTUV1_27R_TRIP
16
NSPTOV1_47-1_TRIP
17
NSPTOV2_47-2_TRIP
18
ROVPTOV2_59N-1_TRIP
Table continues on next page
1MAC109016-MB C
Level trigger mode
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
REF615 ANSI