GUID-A148941E-8D92-4DDB-B497-20582B8FD341 V1 EN
Figure 193:
Current circuit supervision function
The fuse failure supervision SEQSPVC1_60-1 detects failures in the voltage
measurement circuits. Failures, such as an open MCB, raise an alarm.
X120_BI2_CB_CLOSED
GUID-ED37B113-A207-4CE2-9C10-72258E3DF7ED V1 EN
Figure 194:
Fuse failure supervision function
Circuit-breaker condition monitoring SSCBR1_52CM-1 supervises the switch status
based on the connected binary input information and the measured current levels.
SSCBR1_52CM-1 introduces various supervision methods.
Set the parameters for SSCBR1_52CM-1 properly.
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
CB_OPEN_COMMAND
CB_CLOSE_COMMAND
GUID-91B90F36-39AB-4349-AA02-3D32B2F3A94B V1 EN
Figure 195:
Circuit-breaker condition monitoring function
CCSPVC1
BLOCK
FAIL
ALARM
O:11|T:2.5|I:1
SEQSPVC1
BLOCK
FUSEF_3PH
CB_CLOSED
FUSEF_V
DISCON_OPEN
MINCB_OPEN
O:30|T:2.5|I:1
SSCBR1
BLOCK
TRV_T_OP_ALM
POSOPEN
TRV_T_CL_ALM
POSCLOSE
SPR_CHR_ALM
OPEN_CB_EXE
OPR_ALM
CLOSE_CB_EXE
OPR_LO
PRES_ALM_IN
IPOW_ALM
PRES_LO_IN
IPOW_LO
SPR_CHR_ST
CB_LIFE_ALM
SPR_CHR
MON_ALM
RST_IPOW
PRES_ALM
RST_CB_WEAR
PRES_LO
RST_TRV_T
OPENPOS
RST_SPR_T
INVALIDPOS
CLOSEPOS
O:83|T:5|I:1
1MAC109016-MB C
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_ALARM
SEQSPVC1_60-1_FUSEF_3PH
SEQSPVC1_60-1_FUSEF_U
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
REF615 ANSI